Archive
Last modified by Michael Sibayan on 2022/05/03 16:48
Blog - Data-logging and Controls - posts for June 2016
Jun 21, 2016,
Mini LEO data logger software update 2016621030609
At approximately 15:00 on Wednesday, June 21 the LEO Mini data logger software was updated and the logger was restarted.
This update is intended to address an issue with loss of precision of the large counter & volume values of the tipping bucket. The 5-digit level of precision has been removed for all double precision data types within the logging software.
Jun 9, 2016,
Mini LEO calibrations 20160609
Antonio has performed calibrations for the drainage tipping bucket and EC meter. As of today (06/09/2016) the scales for these two devices have been updated on the data logger.
TB - 0.007007 liters per tip
EC = 711.167 * voltage - 124.152