Wiki source code of cRIO-TRF-P01
Last modified by Michael Sibayan on 2022/05/03 16:48
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
1.1 | 1 | [[image:cRIO-TRF-P01.jpg]] |
2 | |||
3 | __Module 1 (NI-9401)__ | ||
4 | * 8 channel digital I/O set up as a pulse counter. | ||
5 | * Used to monitor pulses from anemometers | ||
6 | * Terminal block in the upper right provides power (through a resistor) to the anemometers. | ||
7 | |||
8 | |||
9 | __Module 3 (NI-9205)__ | ||
10 | * 16/32 channel +/-10V analog input | ||
11 | * First 16 channels set up in +/-1V differential mode for the pyranometers and quantum sensors | ||
12 | * Last 16 channels set up in +/-5V referenced single ended mode for the HMP45 temp/RH sensors | ||
13 | * Common is tied to the 12VDC power supply negative terminal (for RSE channels) | ||
14 | |||
15 | __Module 5 (NI-9213)__ | ||
16 | * 16 channel +/- 75mV differential analog input | ||
17 | * First four channels measure light sensor signals | ||
18 | * Channel 5 measures voltage of the PT100 thermistor | ||
19 | * Common is tied to the shields and the 12VDC power supply negative terminal (for PT100) | ||
20 | |||
21 | |||
22 | __0.5mA current source__ | ||
23 | * Provides approximately constant 0.5mA current for the PT-100 thermistor | ||
24 | * 0.5mA chosen to put the signal voltage within range of the NI-9213 AI module (approximately 50mV) | ||
25 | |||
26 | |||
27 | __Anemometer terminal block__ | ||
28 | * Provides 5VDC, through a resistor, to the anemometers | ||
29 | * 5V chosen to match the TTL level of the NI-9401 DIO module | ||
30 |